Moxa  Mfg Mini-Store MOXA Major Lines

Moxa ioLogik E2242-T Ethernet Micro Controller with 4AI and 12DIO, -40 to 75°C, Universal controller, Click&Go

MOXA Major Lines
Mfg Part Number:  ioLogik E2242-T  
Image may not reflect the actual item.
Price: $932.05
Quantity:
Status: Active
No Sales Tax except these states
, PO and Wire.
Manufacturer Warranty Policy:
Moxa's ioLogik E2242 is a new type of active micro controller that can be used as an RTU (Remote Terminal Unit). Active Ethernet micro controllers are a kind of PC-based data acquisition and control device that use proactive, event-based reporting to control I/O devices. Unlike traditional RTUs, which are passive and must poll for data, Moxa's Active OPC Server makes seamless connection with SCADA systems a reality. In addition, SNMP is used for communicating with an NMS (Network Management System) for IT field users. The I/O status of an Active Ethernet micro controller can be reported and controlled automatically on-site based on user specified conditions. This report-by-exception approach, which is new to PC-based monitoring, requires far less bandwidth than traditional polling methods.
  • Front-end intelligence that supports 24 Click&Go™ rules
  • Active Messaging with real-time stamp, including SMS, SNMP Trap with I/O status, TCP, and email
  • Supports SNMPv1/v2c/v3 protocol
  • I/O peer-to-peer function
  • Built-in web console
  • PC utility: Auto detection of installed modules
  • Windows/WinCE VB/VC.NET and Linux C APIs
LAN:
Ethernet 1 x 10/100 Mbps, RJ45
Protection 1.5 KV magnetic isolation
Protocols Modbus/TCP, TCP/IP, UDP, DHCP, Bootp, SNMP, HTTP, CGI, SNTP
Serial:
Interface RS-485-2w: Data+, Data-, GND
Serial Line Protection 15 KV ESD for all signals
Serial Communication Parameters:
Baudrate 1200 to 115200 bps
Data Bits 8
Stop Bits 1
Parity None
Flow Control None
Protocols Modbus/RTU
Analog Input:
Channels 4 analog inputs with differential input
Resolution 16 bits
I/O Mode Voltage / Current
Input Range ±150 mV, 0 to 150 mV, ±500 V, 0 to 500 mV, ±5 V,
0 to 5 V, ±10 V, 0 to 10 V, 0 to 20 mA, 4 to 20 mA
Accuracy ±0.1% FSR @ 25°C
±0.3% FSR @ -10 and 60°C
Sampling Rate (all channels) 100 samples/sec
Input Impedence 200K ohms (min.)
Built-in Resistor for Current Input 102 ohms
DI/DO Configurable Channels:
Channels 12
I/O Mode DI or Event Counter (up to 900 Hz)
DO or Pulse Output (up to 100 Hz)
Digital Input:
Channels Up to 12, source/sink selectable
Sensor Type NPN, PNP, and Dry contact
I/O Mode DI or event counter (up to 900 Hz)
Dry Contact Logic 0: short to GND
Logic 1: Open
Wet Contact (For Source Type)
Logic 0: 0 to 3 VDC
Logic 1: 10 to 30 VDC
(For Sink Type)
Logic 0: 10 to 30 VDC
Logic 1: 0 to 3 VDC
Common Type 6 points per COM
Isolation 3K VDC or 2K Vrms
Counter/Frequency 900 Hz, power off storage
Digital Filtering Time Interval Software selectable
Over-voltage Protection 36 VDC
Poweroff Counter Memory Supports poweroff counter storage function
Digital Output:
Channels Up to 12, sink type, 36 VDC, 200 mA
I/O Mode DO or Pulse Output (up to 100 Hz)
Pulse Wave Width/Frequency 10 ms/100 Hz
Over-voltage Protection 45 VDC
Over-current Limit 400 mA (typical)
Over-temperature Shutdown 175°C (min.)
Output Current Rating Max. 200 mA per channel
Isolation 2K Vrms or 3K VDC (Magnetic)
Power Requirements:
Power Consumption 282 mA typical @ 24 VDC
Power Input 24 VDC nominal, 12 to 36 VDC
Physical Characteristics:
Dimensions 115 x 79 x 45.63 mm (4.53 x 3.11 x 1.80 in)
Wiring I/O cable max. 14 AWG
Environmental Limits:
Operating Temperature -10 to 60°C (14 to 140°F)
Storage Temperature -40 to 85°C (-40 to 185°F)
Ambient Relative Humidity 5 to 95% (non-condensing)
Agency Approvals:
EMI FCC Part 15, CISPR (EN55022) class A
EMS IEC 61000-4, IEC 61000-6
Shock IEC 60068-2-27
Freefall IEC 60068-2-32
Vibration IEC 60068-2-6

Specification

Power Requirements
Power Consumption 178 mA @ 24 VDC
Power Input 24 VDC nominal, 12 to 36 VDC
Serial Communication Parameters
Flow Control None
Protocol Modbus/RTU
Data Bits 8
Parity None
Stop Bits 1
Baudrate 1200 to 115200 bps
Analog Input
Type Differential input
Input Impedance 200K ohms (min.)
Built-in Resistor for Current Input 120 ohms
Resolution 16 bits
Input Range ±150 mV, 0 to 150 mV, ±500 V, 0 to 500 mV, ±5 V, 0 to 5 V, ±10 V, 0 to 10 V, 0 to 20 mA, 4 to 20 mA
Sampling Rate (all channels) 100 samples/sec
Accuracy ±0.1% FSR @ 25°C ±0.3% FSR @ -10 and 60°C
I/O Mode Voltage / Current
Inputs and Outputs
Analog Inputs 4 channels
Configurable DIOs 12 channels
LAN
Protection 1.5 KV magnetic isolation
Ethernet 1 x 10/100 Mbps, RJ45
Protocols Modbus/TCP, TCP/IP, UDP, DHCP, Bootp, SNMP, HTTP, CGI, SNTP
Digital Input
Isolation 3K VDC or 2K Vrms
Poweroff Counter Supports poweroff counter storage function
Common Type 6 points per COM
Over-voltage Protection 36 VDC
Digital Filtering Time Interval Software selectable
Dry Contact • On: short to GND • Off: Open
Wet Contact • On: 0 to 3 VDC • Off: 10 to 30 VDC
Counter Frequency 900 Hz, power off storage
I/O Mode DI or event counter
Sensor Type Wet Contact (NPN or PNP) and Dry Contact
Environmental Limits
Operating Temperature -10 to 60°C (14 to 140°F)
Storage Temperature -40 to 85°C (-40 to 185°F)
Ambient Relative Humidity 5 to 95% (non-condensing)
Physical Characteristics
Weight under 250 g
Dimensions 115 x 79 x 45.6 mm (4.53 x 3.11 x 1.80 in)
Wiring I/O cable max. 14 AWG
Standards and Certifications
EMI FCC Part 15 Subpart B Class A, EN 55022 Class A
Safety UL 508
Shock IEC 60068-2-27
Vibration IEC 60068-2-6
EMS IEC 61000-4, IEC 61000-6
Freefall IEC 60068-2-32
Digital Output
Type Sink
Isolation 2K Vrms or 3K VDC (Magnetic)
Pulse Output Frequency 1 kHz
Over-temperature Shutdown 175°C (min.)
Over-voltage Protection 45 VDC
Current Rating 200 mA per channel
I/O Mode DO or Pulse Output
Over-current Protection 2.6 A (4 channels @ 650 mA)
Serial Communication
Interface RS-485-2w: Data+, Data-, GND
Serial Line Protection 15 KV ESD for all signals
MTBF (mean time between failure)
Time 204,391 hrs
Database Telcordia (Bellcore)
Warranty
Warranty Period 5 years
Details See www.moxa.com/warranty
WARNING:: The plastic used in cable products can expose you to lead and lead components, chemicals known to the State of California to cause cancer, birth defects, or other reproductive harm. For more information go to www.P65Warnings.ca.gov
[0] [true] [Yes] [No] [No]