Output voltage regulation: Battery Mode - PWM sine wave
115V +/-5%
Output frequency regulation: Line Mode - Passes line
frequency of 60Hz +/-10%; Battery Mode - Inverter output
regulated to 60Hz +/-0.5Hz
Outlet quantity / type: 8x NEMA 5-15R
Overload protection: 10A input circuit breaker
Input:
Maximum input amps: 8.5 A
Input connection type: NEMA 5-15P
Input cord length: 6 ft. / 1.8 m
Recommended electrical service: 120V 15A
Battery:
Full load runtime: 3.5 min. (900W)
Half load runtime: 13 min. (450W)
Typical battery lifespan: 4~6 years (depending on usage)
Battery recharge rate: 2~8 hours to 90%
Voltage Regulation:
Voltage regulation description: Automatic Voltage Regulation
(AVR) circuits maintain clean, regulated computer-grade 120V
nominal output, without using battery power, during brownouts to
75V and overvoltages to 147V
Overvoltage correction: Input voltages between 128VAC and
147VAC are reduced by 12%
Brownout correction: Input voltages between 93VAC and
107VAC are boosted by 14%
Severe brownout correction: Input voltages between 75VAC
and 92VAC are boosted by 30%
Surge / Noise Suppression:
AC surge suppression: 480 joules
AC suppression response time: Instantaneous
Dataline suppression: Tel/DSL or Ethernet
EMI / RFI AC noise suppression: Yes
Communications:
Network monitoring port: DB9 and USB
WatchDog compatibility: Compatible with Tripp Lite's
Watchdog system service to restore operation to locked
equipment through soft reboot of application/OS or hard power
off/on reboot of connected equipment; ideal for unattended kiosk
applications
Line / Battery Transfer:
Transfer time from line power to battery mode: 2~4
milliseconds
Low voltage transfer to battery power: Switches to battery
power as line voltage decreases to 75V or less, switches back to
AC mode as line voltage increases to 79V or higher
High voltage transfer to battery power: Switches to battery
mode as line voltage increases to 147V or higher, switches back
to AC mode as line voltage decreases to 143V or lower
Certifications: Tested to UL1778 (USA), CSA (Canada), NOM
(Mexico), Class B (EMI), FCC part 68 and Industry Canada (US
& Canada)
Special Features:
Cold Start: Yes, inverter can be "cold started" to enable
temporary AC output during a power failure
Appearance: Attractive black color scheme
Physical:
Material of construction: ABS
Form factors supported: Rack/Tower
Cooling method: Convection
Dimensions (WxDxH): 3.5 x 10.5 x 17.25 inch / 8.9 x 26.7 x
43.8 cm
WARNING:: The plastic used in cable products can expose you to lead and lead components,
chemicals known to the State of California to cause cancer, birth defects, or other reproductive harm.
For more information go to www.P65Warnings.ca.gov
[0] [true] [Yes] [No] [No]
Same card, added safety online.
Verified by Visa is a new service that lets you shop online with added confidence.
Through a simple checkout process, Verified by Visa confirms your identity when you make purchases at participating online stores. It's convenient, and it works with your existing Visa card.
Plus, Verified by Visa is a snap to use. You register your card just once, and create your own password. Then, when you make purchases at participating online stores, a Verified by Visa window will appear. Simply enter your password and click submit. Your identity is verified and the purchase is secure.
To activate Verified by Visa in your Visa card, or to learn more, contact the financial institution that issued your Visa card or visit
visa.com/verified.