Each input circuit is switch selectable for slow/fast filter that has a 4.7 millisecond time constant. The filter must be selected for AC inputs in order to eliminate response to AC noise. The filter is also valuable for use with slow DC input signals in a noisy environment. The filter may be switched out for DC inputs in order to obtain faster response. Filters are manually switched individually on or off.
Isolated Digital Inputs
- Number of Inputs: Eight
- Type: Non-polarized, optically-isolated from each other and from the computer. (CMOS compatible).
- Voltage Range: 3 to 31V DC or AC RMS (50 to 10KHz)
- Isolation: 500V
- Input Resistance: 1.8K? in series with an opto-coupler
- Response Time: 4.7 milliseconds w/filter, 10 µsec w/o filter
TTL Digital Inputs
- Number of Inputs: Eight
- Type: TTL, 10K pull up to 5V
- Purpose: For reading dry contact closures or any TTL compatible outputs
Relay Outputs
- Number of Outputs: Eight
- Type: SPDT Form C Relay - Omron G5V-1
- Contact Ratings: 1A @ 24VDC (60VDC max), 0.5A @ 125VAC carry current
- Contact Type: Single crossbar Ag with Au clad (bifurcated contacts optional)
- Contact Arrangements: Channels 0-7: SPDT Form C
- Contact Resistance: Initial, 100 m? maximum
- Contact Life: Mechanical: 5 million operations minimum
- Operating Time: 5 milliseconds maximum
- Release Time: 5 millisecond maximum
- Regulatory Approvals: UL and CSA
Interrupts
- When enabled by software, interrupts are generated when any isolated digital input changes state (High to Low or Low to High, and from signal to no signal with AC inputs).
Power Required
- +5VDC at 0.4A (all relays ON)
Environmental
- Ambient Temperature: Operating: -30°C to 70°C (Non-Icing)
- Weight: Approx. 4 oz. (~115 grams)