, PO and Wire.
Ideal UPS Backup in Healthcare Facilities
Reliable Battery Backup and Surge Protection
LEDs and Audible Alarms
Saves Files When You're Away
| General Information | |
| Manufacturer | Eaton Corporation |
| Manufacturer Part Number | SMART1200XLHG |
| Manufacturer Website Address | https://tripplite.eaton.com/ |
| Brand Name | Tripp Lite by Eaton |
| Product Line | SmartPro |
| Product Name | SmartPro 1200XLHG UPS |
| Product Type | Line-interactive UPS |
| Technical Information | |
| Plug/Connector Type | NEMA 5-15P |
| Receptacle Type | NEMA 5-15R |
| Receptacle Detail | 4 x NEMA 5-15R |
| Cord Length | 6 ft |
| Transfer Time | 4 ms |
| Power Description | |
| Load Capacity (VA) | 1000 VA |
| Load Capacity (Watt) | 750 W |
| Input Voltage | 120 V AC |
| Output Voltage | 115 V AC |
| Output Voltage | 120 V AC |
| Management | |
| Network Management | SNMP Manageable |
| Alarm | Overload |
| Alarm | Low Battery |
| Alarm | On Battery |
| Controls/Indicators | |
| Status Indicators | Includes 5 front-panel indicator LEDs to show battery charge level, AC line voltage levels, automatic voltage regulation status, UPS load level and replace battery warning |
| Interfaces/Ports | |
| USB | Yes |
| Battery Information | |
| Battery Chemistry | Lead Acid |
| Backup/Run Time (Full Load) | 10 Minute |
| Backup/Run Time (Half Load) | 28 Minute |
| Battery Life | 6 Year |
| Typical Battery Recharge Time | 4 Hour |
| Hot Swappable | Yes |
| Environmental Conditions | |
| Maximum Operating Temperature | 104°F (40°C) |
| Physical Characteristics | |
| Height | 12.8" |
| Width | 7.5" |
| Depth | 9" |
| Form Factor | Tower |
| Weight (Approximate) | 44.60 lb |
| Miscellaneous | |
| Package Contents |
|
| Additional Information |
|
| Certifications & Standards | UL1778 (USA, Series AGSM1200PSR3HG), UL2601-1 (Medical), cUL (Canada), FCC Class A (emissions), Conforms to IEEE 587 / ANSI C62.41 specifications |
| Country of Origin | Taiwan |
| Warranty | |
| Limited Warranty | 2 Year |
| General Information | |
| Power Rating | 1000 VA |
| Output Voltage Rating | 120 V |
| Number of Outputs | 4 |
| Runtime-Full Load | 16 min |
| Runtime-Half Load | 34 min |
| SYSTEM OVERVIEW | |
|
System overview:
|
Medical Grade tower UPS system includes built
in isolation transformer with faraday shield, line interactive voltage
regulation. AC surge suppression, RS-232 & USB monitoring ports
with complete software and cabling, plus hospital-grade plug and
outlets. Runtime is expandable via separate purchase BP36V27 external
battery packs. UL 60601-1 listed as medical electrical equipment with
less than 300 microamps combined leakage current for UPS and connected
loads.
|
|
Voltage compatibility:
|
120V AC
|
|
Frequency compatibility:
|
60 Hz
|
| OUTPUT | |
|
Output volt amp capacity (VA):
|
1000
|
|
Output watt capacity (watts):
|
750
|
|
Output nominal voltage:
|
120V AC
|
|
Output voltage regulation:
|
LINE MODE: Sine wave line voltage 120V (-18% /
+8%)
BATTERY MODE: PWM sine wave output 115V +/-5% |
|
Output frequency regulation:
|
LINE MODE: Passes line frequency of 60Hz +/-10%
BATTERY MODE: Inverter output regulated to 60Hz +/-0.5Hz |
|
Outlet quantity / type:
|
4 NEMA 5-15R HG
|
|
Overload protection:
|
Resettable circuit breaker
|
| INPUT | |
|
Maximum input amps:
|
9.2A / 860 watts
|
|
Input connection type:
|
NEMA 5-15P HG
|
|
Input cord length:
|
6 ft., 14 gauge
|
|
Recommended electrical service:
|
15A 120V
|
| BATTERY | |
|
Full load runtime:
|
16 min. (1000VA)
|
|
Half load runtime:
|
34 min. (500VA)
|
|
Expandable battery runtime:
|
Supports extended runtime with optional BP36V27
external battery pack (multi-pack compatible)
|
|
DC system voltage:
|
36V DC
|
|
Typical battery lifespan:
|
3-6 years, depending on usage
|
|
Battery recharge rate:
|
2-4 hours to 90%
|
| VOLTAGE REGULATION | |
|
Voltage regulation description:
|
Line interactive UPS offers 2 boost levels of
brownout correction and a single level of overvoltage adjustment to
maintain usable, computer grade output without consuming battery power
over an input voltage range of 81 to 143V AC.
|
|
Overvoltage correction:
|
Input voltages between 126 and 143V AC are
reduced by 9%
|
|
Direct pass through:
|
Input voltages between 105 and 125V AC are
passed through unchanged
|
|
Brownout correction:
|
Input voltages between 96 and 106V AC are
boosted by 10%
|
|
Severe brownout correction:
|
Input voltages between 81 and 95V AC are
boosted by 21%
|
| LEDS ALARMS & SWITCHES | |
|
Front panel LEDs:
|
Yes, includes 5 front-panel indicator LEDs to
show battery charge level, AC line voltage levels, automatic voltage
regulation status, UPS load level and replace battery warning
|
|
Alarms:
|
3 function audible alarm indicates power
failure conditions (4 short beeps every 10 seconds), overload
(continuous short beeps) and low battery (continuous tone)
|
|
Switches:
|
Yes, includes 2 front panel mounted push-button
switches for system enable, self-test and alarm cancel functions
|
| SURGE / NOISE SUPPRESSION | |
|
AC surge suppression:
|
480 joules
|
|
AC suppression response time:
|
Instantaneous
|
|
EMI / RFI AC noise suppression:
|
Yes
|
| PHYSICAL | |
|
Shipping weight (lbs):
|
49.2
|
|
Shipping weight (kg):
|
22.4
|
|
Unit weight (lbs):
|
45.2
|
|
Unit weight (kg):
|
20.5
|
|
Unit Dimensions (HWD/in):
|
12.5 x 7.5 x 9.5
|
|
Unit Dimensions (HWD/cm):
|
31.75 x 19.1 x 24.2
|
|
Shipping Dimensions (HWD/in):
|
18.25 x 11.75 x 13.5
|
|
Shipping Dimensions (HWD/cm):
|
46.4 x 29.9 x 34.3
|
|
Material of construction:
|
PVC
|
|
Form factors supported:
|
Tower
|
|
Cooling method:
|
UPS cooling via rear-exit fan
|
|
Battery Access:
|
Battery access door allows hot swap battery
replacement without powering connected equipment off
|
| ENVIRONMENTAL | |
|
Operating Temperature:
|
+32 to +104 degrees Fahrenheit
0 to +40 degrees Celsius |
|
Storage Temperature:
|
+5 to +122 degrees Fahrenheit
-15 to +50 degrees Celsius |
|
Relative Humidity:
|
0 to 95%, non-condensing
|
| COMMUNICATIONS | |
|
Network monitoring port:
|
Includes 2 built-in monitoring ports, 1 USB
& 1 DB9
|
|
Software and cabling included:
|
PowerAlert UPS monitoring software is included
on CD-ROM for all common network and standalone operating systems.
Ships with 2 cables, 1-USB to USB & 1-DB9 to DB9
|
| LINE / BATTERY TRANSFER | |
|
Transfer time from line power to
battery mode:
|
2-4 milliseconds
|
|
Low voltage transfer to battery power:
|
81V (resets to line power as voltage increases
to 85V)
|
|
High voltage transfer to battery power:
|
143V (resets to line power as voltage decreases
to 139V)
|
| CERTIFICATIONS | |
|
Certifications:
|
UL1778 (USA, Series AGSM1200PSR3HG), UL 60601-1
(Medical), cUL (Canada), Class A (Emissions)
|
| WARRANTY | |
|
Optional coverage:
|
3-year, 5-year, next day and on-site warranty
coverage available in many areas; contact Tripp Lite
|
|
Product warranty:
|
2 year product warranty
|
| SPECIAL FEATURES | |
|
Cold Start:
|
Yes, inverter can be cold started to enable
temporary AC output during a power failure
|
|
Appearance:
|
Attractive gray tower UPS
|

WARNING:: The plastic used in cable products can expose you to lead and lead components,
chemicals known to the State of California to cause cancer, birth defects, or other reproductive harm.
For more information go to www.P65Warnings.ca.gov