, PO and Wire.
The ICF-1170I series CANbus-to-fiber converters are used to convert CAN signals from copper to optical fiber. The converters come with 2 KV optical isolation for the CANbus system and dual power inputs with alarm contact relay to ensure that your CANbus system will remain online.
| CAN Communication | |
| CANbus Interface | ISO 11898-2, Terminals (CAN_H, CAN_L,CAN_ GND) |
| Protocols | CAN 2.0A and 2.0B (ISO 11898-2) |
| Connector Type | 3-pin removable screw terminal x1 |
| Termination Resistor | Dip switch selector for 120 ? terminal resistor |
| Buadrate | Up to 1 Mbps |
| System Delay | 150 ns |
| Isolation Protection | 2 KV |
| Transmission Distance | Max 2 km (depends on the data rate and the protocol used) |
| LED Indicators | PWR1, PWR2, Fiber TX, Fiber RX |
| Note | The transmission distance is limited by the signal rate, as mentioned in the ISO 11898-2 standard |
| Fiber Communication | |
| Connector Type | ST (multi-mode) fiber ports x 2 |
| Support Cable | 50/125, 62.5/125, or 100/140 ?m (multi-mode) |
| Wavelength | 850 nm |
| Tx Output | Multi-mode (> -5 dBm) |
| RX Sensitivity | Multi-mode (-20 dBm) |
| Physical Characteristics | |
| Housing | Aluminum (1 mm) |
| Dimensions | 30.3 x 70 x 115 mm (11.9x27.6x45.3 in) |
| Environmental Limits | |
| Operating Temperature | Standard Models: 0 to 60°C (32 to 140°F) Wide Temp. Models: -40 to 85°C (-40 to 185°F) |
| Operating Humidity | 5 to 95% RH |
| Storage Temperature | -40 to 85°C (-40 to 185°F) |
| Power Requirements | |
| Input Voltage | 12 to 48 VDC dual power inputs for redundant power |
| Power Consumption | ICF-1170I: 221 mA @ 12 V Alarm Contact: 1 relay output with current carrying of 1 A @ 24 VDC |
| Voltage Reversal Protection | Protects against V+/V- reversal |
| Over Current Protection | 1.1 A (protects against two signals shorted together) |
| Regulatory Approvals | |
| EMI | EN55022 1998, Class A |
| EMS | EN61000-4-2 (ESD), Criteria B, Level 4 EN61000-4-3 (RS), Criteria A, Level 2 EN61000-4-4 (EFT), Criteria B, Level 4 EN61000-4-5 (Surge), Criteria B, Level 2 EN61000-4-6 (CS), Criteria B, Level 2 En61000-4-8 (PFMF), Criteria A, Level 3 |
| UL/CUL | UL-508 |
| TUV | EN 60950-1 |
| CE | Class A |
| FCC | Part 15 sub Class A |
| Freefall | IEC 60068-2-32 |
| MTBF | 792085 hrs |
| Warranty | |
| Warranty Period | 5 years |
| Power Requirements | |
| Power Consumption | ICF-1170I: 221 mA @ 12 V Alarm Contact: 1 relay output with current carrying of 1 A @ 24 VDC |
| Input Voltage | 12 to 48 VDC dual power inputs for redundant power |
| Voltage Reversal Protection | Protects against V+/V- reversal |
| Over Current Protection | 1.1 A (protects against two signals shorted together) |
| Fiber Communication | |
| Wavelength | 850 nm |
| Rx Sensitivity | Multi-mode (-20 dBm) |
| Connector Type | ST (multi-mode) fiber ports |
| TX Output | Multi-mode (> -5 dBm) |
| Support Cable | 50/125, 62.5/125, or 100/140 μm (multi-mode) |
| Environmental Limits | |
| Operating Temperature | Standard Models: 0 to 60°C (32 to 140°F) Wide Temp. Models: -40 to 85°C (-40 to 185°F) |
| Storage Temperature | -40 to 85°C (-40 to 185°F) |
| Ambient Relative Humidity | 5 to 95% (non-condensing) |
| MTBF (mean time between failures) | |
| Time | 792,085 hrs |
| Database | Telcordia (Bellcore), GB |
| CAN Communication | |
| Note | The transmission distance is limited by the signal rate, as indicated in the ISO 11898-2 standard. |
| Transfer Rate | Up to 1 Mbps |
| Protocols | CAN 2.0A and 2.0B (ISO 11898-2) |
| Isolation Protection | 2 KV |
| Transmission Distance | Max 2 km (depends on the data rate and the protocol used) |
| System Delay | 150 ns |
| Connector Type | 3-pin removable screw terminal x1 |
| ESD Protection | Supports 15 KV |
| LED Indicators | PWR1, PWR2, Fiber TX, Fiber RX |
| CAN Interface | ISO 11898-2, Terminals (CAN_H, CAN_L,CAN_GND) |
| Termination Resistor | Dip switch selector for 120 Ω terminal resistor |
| Physical Characteristics | |
| Weight | Product only: 175 g (0.39 lb) Packaged: 320 g (0.71 lb) |
| Dimensions | 30.3 x 70 x 115 mm (1.19 x 2.76 x 4.53 in) |
| Housing | Aluminum (1 mm) |
| Standards and Certifications | |
| EMI | EN 55022 Class A, FCC Part 15 Subpart B Class A |
| Safety | UL 508, EN 60950-1 |
| EMS | EN 61000-4-2 (ESD) Level 4, EN 61000-4-3 (RS) Level 2, EN 61000-4-4 (EFT) Level 4, EN 61000-4-5 (Surge) Level 3, EN 61000-4-6 (CS) Level 2, EN 61000-4-8 (PFMF) Level 3 |
| EMC | CE, FCC |
| Freefall | IEC 60068-2-32 |
| Green Product | RoHS, CRoHS, WEEE |
| Warranty | |
| Warranty Period | 5 years |
| Details | See http://www.moxa.com/support/warranty.htm |
If you need accessory information for this product, please use our Online Contact Us Form , our industrial sales team is here to help you find the accessories.
WARNING:: The plastic used in cable products can expose you to lead and lead components,
chemicals known to the State of California to cause cancer, birth defects, or other reproductive harm.
For more information go to www.P65Warnings.ca.gov