Special Note: Jan 05, 2020
NCNR; If you do not have loading facility, please contact our CST for special handling service.

, PO and Wire.
| General Information | |
| Manufacturer | Eaton Corporation |
| Manufacturer Part Number | PW9S9K-PD |
| Manufacturer Website Address | http://www.eaton.com |
| Brand Name | Eaton |
| Product Name | 9170+ Rackmount UPS 9 to 18 kVA UPS |
| Product Type | Online UPS |
| Technical Information | |
| Plug/Connector Type | Hardwired |
| Receptacle Type | NEMA 5-20R |
| Receptacle Type | NEMA L14-30R |
| Receptacle Type | NEMA L6-30R |
| Receptacle Detail | 2 x NEMA L6-30R |
| Receptacle Detail | 12 x NEMA 5-20R |
| Receptacle Detail | 2 x NEMA L14-30R |
| Power Description | |
| Load Capacity (VA) | 9000 VA |
| Input Voltage | 110 V AC |
| Input Voltage | 220 V AC |
| Output Voltage | 208 V AC |
| Output Voltage | 120 V AC |
| Output Voltage | 240 V AC |
| Input Frequency | 60 Hz |
| Output Frequency | 60 Hz |
| Waveform Type | Sine Wave |
| Management | |
| Alarm | Low Redundancy Insufficient Battery |
| Alarm | Check Memory |
| Alarm | Low Runtime |
| Alarm | Output Overload |
| Alarm | High AC Input |
| Alarm | Low AC Output |
| Alarm | Emergency Power Off |
| Alarm | Check Battery Weak Battery |
| Alarm | Check Battery Open Cell |
| Alarm | Excessive Transfer |
| Alarm | Module Failure |
| Alarm | Overload Shutdown |
| Alarm | High AC Output |
| Alarm | Low Battery |
| Alarm | Check Battery |
| Alarm | High Heatsink Temperature |
| Alarm | Phase Error |
| Alarm | Low Redundancy Insufficient Module |
| Alarm | Incompatible Module |
| Alarm | High Battery |
| Alarm | Fan Failure |
| Alarm | Precharge Failure |
| Bypass Switch | Automatic |
| Emergency Power OFF | Yes |
| Controls/Indicators | |
| Status Indicators |
|
| Interfaces/Ports | |
| Modular Slots | 2 x Communications Slot |
| Battery Information | |
| Battery Characteristics | Maintenance-free |
| Battery Chemistry | Lead Acid |
| Backup/Run Time (Full Load) | 8 Minute |
| Backup/Run Time (Half Load) | 24 Minute |
| Typical Battery Recharge Time | 4 Hour |
| Environmental Conditions | |
| Maximum Operating Temperature | 104°F (40°C) |
| Sound Emission (A-Weighted) | 50 dB(A) |
| Miscellaneous | |
| Additional Information |
|
| Certifications & Standards |
|
| Warranty | |
| Limited Warranty | 2 Year |
WARNING:: The plastic used in cable products can expose you to lead and lead components,
chemicals known to the State of California to cause cancer, birth defects, or other reproductive harm.
For more information go to www.P65Warnings.ca.gov